|

The installer of
this particular ground fault circuit breaker was confused, The way this thing was
wired, caused the GFCI to never engage, or turn power on to
the circuit.
Notice in the
lower left, all of the neutrals and ground wires in the box
are tied to the neutral bus bar. Also take note that the
pigtail from the gfci is floating with a red wire nut on it.
This is all wrong.
The white pigtail
must be connected directly to the neutral bus bar in order for
the ground fault circuit breaker to operate. The white
neutral wire going to the bus bar from the spa must be
installed in the neutral terminal in the gfci.
The best
practices method of installing this box, would be to tie the
neutrals to the bus bar, and connect the grounds separately,
and tie them to the ground bonding bar inside the box
(diagonal looking strip of metal underneath the wires,
attached to the back of the box). The neutral bar in this box
is actually isolated from ground.
|